1. Piercing connector, simple installation, need not strip the cable coat.
2. Moment nut, piercing pressure is constant keep good electric connection and make no damage to lead.
3. Self-seam frame waterproof and anti-corrosion, extend the using life of insulated lead and connection.
4. Adopted special connecting tablet, apply to joint of Cu(Al)and Cu(Al)or Cu and Al.
5. Small electric connecting resistance, connecting resistance less than 1.1 times of the resistance of branch conductor with the same length.
6. Special insulated case body, resistance to illumination and environmental aging, the insulation strength can up to 12KV.
7. Arc surface design, apply to connection with the same (different)diameter, wide connection scope(0.75mm2-400mm2) .
Performance testing
- Mechanical performance: the grip force of the wire clamp is 1/10 bigger than the break force of the lead .It comply with GB2314-1997.
- Temperature rise performance: under the condition of big current, the temperature rise of connector is less than that of connection lead.
- Heat circle performance: conforms to GB/T2317.3-2000, the heat circle trial standard for electric fitting .
- Waterproof insulation performance conforms to the relevant requirements in Part 2 of GB/T13140.4-1998 .
- Resistance to corrosion performance: under the condition of SO, and salt fog, it can do three times of fourteen days circle testing.
- Environmental aging performance: under the circumstance of ultraviolet, radiation, dry and moist, expose if with change of temperature and heat impulse for six weeks .
- Fire-proof performance: insulation material of the connector withstands glowing filament test Conform to the requirements in Chapter4-10 of GB/T5169.4
Product type and application scope 1KV Series products (Low voltage series)
Model |
Main line section |
Branch section |
Nominal current |
Outline |
Weight |
Piercing Depth |
PM756 |
0.75-6 |
0.75-6 |
41 |
21×27×23 |
10 |
1-1.5 |
PM041 |
6-10 |
1.5-6 |
41 |
26×39×54 |
85 |
1.5-2 |
PM101 |
1.5-2.5 |
1.5-10 |
55 |
27×41×62 |
55 |
1.5-2 |
PMEP |
16-95 |
1.5-10 |
55 |
27×41×62 |
55 |
1-2 |
PM2-95 |
16-95 |
4-35(50) |
157 |
46×52×87 |
160 |
1.5-2 |
PM2-150 |
50-150 |
6-35(50) |
157 |
46×52×87 |
162 |
1.5-2.5 |
PM3-95 |
25-95 |
25-95 |
214 |
50×61×100 |
198 |
1.5-2 |
PM4-150 |
50-150 |
50-150 |
316 |
50×61×100 |
219 |
1.5-2.5 |
PM6 |
120-240 |
25-120 |
211 |
52×68×100 |
360 |
1.5-2.5 |
PM7 |
150-240 |
10-25 |
102 |
52×68×100 |
336 |
1.5-2.5 |
PM240 |
95-240 |
95-240 |
425 |
83×130×130 |
1040 |
1.5-2.5 |
PM300 |
300 |
ANY |
425 |
83×130×130 |
1040 |
1.5-2.5 |
PM400 |
400 |
ANY |
425 |
83×130×130 |
1040 |
1.5-2.5 |
Piercing connector (10kV)
Application to branch connection and succession for 10kV insulated overhead distribution systems.
Technical Data
Model |
Application cable (mm2) |
Dimensions (mm2) |
Nominal |
Bolt No . |
Main application |
|||
Main line |
Branch line |
A |
B |
H |
||||
PMC10-300/300 |
150-300 |
150-300 |
100 |
85 |
135 |
600 |
2 |
The connection of main |
PMC10-300/150 |
150-300 |
35-150 |
92 |
83 |
118 |
342 |
2 |
|
PMC10-240/240 |
95-240 |
95-240 |
90 |
85.5 |
113 |
476 |
2 |
|
PMC10-240/150 |
95-240 |
50-150 |
85.5 |
83 |
113 |
342 |
2 |
|
PMC10-240/50 |
95-185 |
16-50 |
76 |
83 |
113 |
162 |
2 |
|
PMC10-185/50 |
95-185 |
16-50 |
78.5 |
80.5 |
113 |
162 |
2 |
|
PMC10-95/70 |
25-95 |
16-70 |
68 |
82.5 |
97.5 |
207 |
2 |
Piercing grounding protection (20kV)
Application to grounding protection during electric power construction for 20kV or below insulated overhead line.
Technical Data
Model |
Application cable (mm2) |
Dimensions (mm2) |
Nominal |
Bolt No . |
Main application |
|||
Main line |
Branch line |
A |
B |
H |
||||
PMCF20-120/35 |
20 |
35-120 |
166 |
140 |
123 |
299 |
2 |
The grounded safety protection |
PMCF20-240/150 |
20 |
150-240 |
170 |
140 |
140 |
476 |
2 |